Descrizione
UPS ATLANTIS A03-OP6002P-RC 6000VA/5400W RACK 6U (3+3) DOPPIA CONV.-INTERF.EPO-16 BATT. 12V/7A -SLOT X SK SNMP
Power Rating (VA): 6000
Power Rating (W): 5400
Input (Low Line Transfer):
– 80VAC-300VAC (load <=30%±5%)
– 140VAC-300VAC (load <=60%±5%)
– 160VAC-300VAC (load <=80%±5%)
– 190VAC-300VAC (load <=100%±5%)
Frequency Range: 45-55Hz / 54-66Hz
Power Factor: >0,99 (Normal Voltage)
Output
– Voltage: 208/220/230/240VAC
– AC Voltage Regulation: ±1%
– Frequency Range: 50Hz (±0.5%) or 60Hz (±0.5%)
– Waveform: Pure SineWave
– Crest Ratio: 3:1 (Max)
– Harmonic Distortion: <2% THD (liner Load) | <5% THD (Non liner Load)
Transfer:
– AC->Battery: Zero
– INV->ByPass: Less than 4ms (typical)
WaveForm (Batt. Mode): Pure Sinewave
Efficiency:
– AC Mode = 92%
– Battery = 90%
– ECO = 96%
Battery
– Voltage: 192VDC
– Capacity: 12V/7.0Ah
– Quantity: 16
– Recharge Time: 5 hours to (90%)
– Type: Sealed Maintenance Free Lead Acid VRLA Type
– Design: Easy-swappable battery design
– Charging Voltage: 218.4 VDC ±1%
– Charging I: 1.0A Max
Indicators LCD Display
– UPS status | Load level | Battery level | Input/Output/battery info | Discharge time and Fault indicators
Backup Times:
– 2700w up to 3:20m
– 2025w up to 5:20m
– 1350w up to 11m
– 675w up to 25m
Protection:
– 105%< Overload AC <110% Overload Warning UPS transfers to ByPass after 10 minutes
– 110%< Overload AC <130% Overload Warning UPS transfers to ByPass after 1 minutes
– Overload AC >130% Overload Warning UPS transfers to ByPass after 3 seconds
– 105%< Overload Battery <110% Overload Warning UPS shut down after 10 minutes
– 110%< Overload Battery <130% Overload Warning UPS shut down after 1 minute
– Overload AC >130% Overload Warning shut down after 3 seconds
– 110%< ByPass <120% Overload Warning UPS shut down after 30 minutes
– 120%< ByPass <130% Overload Warning UPS shut down after 10 minutes
– ByPass >130% Overload Warning UPS shut down after 1 minute
– Overload Inverter (>100%)
– Short Circuit INV: Electric Circuit
– Short Circuit AC: ICB & Electric Circuit
– Battery Over-drain Two stages: Controlled Battery Low Warning & Cut Off
– High Surge Level Immunity (>7KV)
Advanced:
– Fan detect protection and Fan speed control
– ECO mode
Connections
– Terminal Block
– RS232 and USB(HID)
– Intelligent Slot for SNMP Card (A03-SNMP2-IN)
– EPO/ROO
– Battery Box Connection
Dimensions (WxHxD):
– Ups: 438 x 131 (3U) x 480 mm
– Battery Pack: 438 x 131 (3U) x 680 mm
Weight: 59,4 Kg
Noise Level: Less then 55 dBA @ 1.0 meter (battery full charged, without buzzer)
Temperature: 0°-40° C
Humidity: 20-90% (non-condensing)




Recensioni
Ancora non ci sono recensioni.