In offerta

UPS ATLANTIS A03-OP3002P 3000VA/2700W DOPPIA CONVERS., SMART BATT. INTERF.USB/RS232/EPOMANAG.-6 BATT.12V 9A/H (SOST.A FINO:30/04

675,67

UPS ATLANTIS A03-OP3002P 3000VA/2700W DOPPIA CONVERS., SMART BATT. INTERF.USB/RS232/EPOMANAG.-6 BATT.12V 9A/H (SOST.A
PROMO
In arrivo 4 pz il 1799-12-31

5 disponibili

COD: A03-OP3002P Categoria:

Descrizione

UPS ATLANTIS A03-OP3002P 3000VA/2700W DOPPIA CONVERS., SMART BATT. INTERF.USB/RS232/EPOMANAG.-6 BATT.12V 9A/H (SOST.A

Power Rating (VA): 3000
Power Rating (W): 2700

Input:
– 80VAC-300VAC (load <=30%±5%)
– 140VAC-300VAC (load <=60%±5%)
– 160VAC-300VAC (load <=80%±5%)
– 190VAC-300VAC (load <=100%±5%)
Frequency Range: 40Hz to 70Hz
Power Factor: >0,99 (Normal Voltage)

Output:
– Voltage: 208/220/230/240VAC
– AC Voltage Regulation: ±1% 
– Frequency Range: 50Hz (±0.5%) or 60Hz (±0.5%)
– Waveform: Pure SineWave
– Crest Ratio Current 3:1 (Max)
– Harmonic Distortion (THDU): min 3% THD (liner Load) / min 5% THD (Non liner Load)

Transfer:
– AC->Battery: Zero
– INV->ByPass: Less than 4ms (typical)
WaveForm (Batt. Mode): Pure Sinewave

Efficiency:
– AC Mode = 91%
– Battery = 88%
– ECO = 97%

Battery:
– Voltage: 72VDC
– Capacity: 12V/9.0Ah
– Quantity: 6
– Recharge Time: 4 hours to (90%)
– Type: Sealed Maintenance Free Lead Acid VRLA Type
– Design: Swappable battery design
– Charging Voltage: 82,1VDC ±1%
– Charging Current: 1.5A Max

Indicators (display LCD):
– UPS status, Load level, Battery level, Input/Output/battery info, Discharge time and Fault indicators

Backup Time:
– 2700w up to 3:20m
– 2025w up to 5:20m
– 1350w up to 11m
– 675w up to 25m

Protection:
– 105% < Overload AC <110% Overload Warning UPS Only
– 110% < Overload AC <130% Overload Warning UPS transfers to ByPass after 1 minutes
– Overload AC >130% Overload Warning UPS transfers to ByPass after 3 seconds
– 105% < Overload Battery <110% Overload Warning UPS
– 110% < Overload Battery <130% Overload Warning UPS shut down after 1 minute
– Overload AC >130% Overload Warning shut down after 3 seconds
– 110% < ByPass <120% Overload Warning UPS shut down after 30 minutes
– 120% < ByPass <130% Overload Warning UPS shut down after 10 minutes
– ByPass >130% Overload Warning UPS shut down after 1 minute
– Overload Inverter (>100%)
– Short Circuit INV: Electric Circuit
– Short Circuit AC: ICB & Electric Circuit
– Battery Over-drain Two stages: Controlled Battery Low Warning & Cut Off
– High Surge Level Immunity(>7KV)
Advanced: Fan detect protection and Fan speed control | ECO mode

Connections:
– Output 4xIEC 320 C13 (Battery Power Supplied) + 1xTerminal Block
– RS232 and USB(HID)
– Intelligent Slot for SNMP Card
– EPO/ROO
– Battery Bank Connection

Dimensions (WxHxD): 196 x 342 x 416 mm
Net Weight 21,3 Kg (with Battery)
Temperature: 0°-40° C
Humidity: Humidity 20-90% (non-condensing)
Noise level: Less then 50 dBA @ 1.0 meter (battery full charged, without buzzer)

Recensioni

Ancora non ci sono recensioni.

Solamente clienti che hanno effettuato l'accesso ed hanno acquistato questo prodotto possono lasciare una recensione.

Ti informiamo non appena sarà nuovamente disponibile. Inserisci un email valida.