Descrizione
UPS ATLANTIS A03-OP1002 1000VA/900W DOPPIA CONVERS.,SMART BATT.MANAG.INTERFACCIA USB/EPO -2 BATT. 12V/9A (SOST.A03-OP
Power Rating (VA): 1000
Power Rating (W): 900
Input:
– 110VAC-300VAC (load <=50%±5%)
– 140VAC-300VAC (load <=70%±5%)
– 160VAC-300VAC (load <=80%±5%)
– 180VAC-300VAC (load <=100%±5%)
Frequency Range: 40Hz to 70Hz
Power Factor: >0,99 (Normal Voltage)
Output:
– Voltage: 208/220/230/240VAC
– AC Voltage Regulation: ±1%
– Frequency Range: 50Hz (±0.5%) or 60Hz (±0.5%)
– Waveform: Pure SineWave
– Crest Ratio Current 3:1 (Max)
– Harmonic Distortion (THDU): min 3% THD (liner Load) / min 6% THD (Non liner Load)
Transfer:
– AC->Battery: Zero
– INV->ByPass: Less than 4ms (typical)
WaveForm (Batt. Mode): Pure Sinewave
Efficiency:
– AC Mode = 89%
– Battery = 85%
– ECO = 95%
Battery:
– Voltage: 24VDC
– Capacity: 12V/9.0Ah
– Quantity: 2
– Recharge Time: 4 hours to (90%)
– Type: Sealed Maintenance Free Lead Acid VRLA Type
– Design: Swappable battery design
– Charging Voltage: 27,4VDC ±1%
– Charging Current: 1.0A Max
Indicators (display LCD):
– UPS status, Load level, Battery level, Input/Output/battery info, Discharge time and Fault indicators
Backup Time:
– 900w up to 2:30m
– 675w up to 5:30m
– 450w up to 9 m
– 225w up to 22m
Protection:
– 105% < Overload AC < 110% Overload Warning UPS.Transfer to Bypass after 10 minutes
– 110% < Overload AC < 130% Overload Warning UPS. Transfers to ByPass after 1 minute
– Overload AC > 130% Overload Warning UPS transfers to ByPass after 3 seconds
– 105% < Overload Battery <110% Overload Warning UPS, shut down after 10 minutes
– 110% < Overload Battery <130% Overload Warning UPS shut down after 1 minute
– Overload AC >130% Overload Warning shut down after 3 seconds
– 110% < ByPass <120% Overload Warning UPS shut down after 30 minutes
– 120% < ByPass <130% Overload Warning UPS shut down after 10 minutes
– ByPass > 130% Overload Warning UPS shut down after 1 minute
– Overload Inverter (>100%)
– Short Circuit INV: Electric Circuit
– Short Circuit AC: ICB & Electric Circuit
– Battery Over-drain Two stages: Controlled Battery Low Warning & Cut Off
– High Surge Level Immunity (>7KV)
Advanced: Fan detect protection and Fan speed control | ECO mode
Connections:
– Output 4xIEC 320 C13 (Battery Power Supplied)
– RS232 and USB(HID)
– Intelligent Slot for SNMP Card
– EPO/ROO
Dimensions (WxHxD): 140 x 191 x 327 mm
Net Weight 10,1 Kg (with Battery)
Temperature: 0°-40° C
Humidity: Humidity 20-90% (non-condensing)
Noise level: Less then 50 dBA @ 1.0 meter (battery full charged, without buzzer)